Description
Standby Power: 220kVA@ 230/400v | 50Hz | 1500rpm
Volvo six-cylinder water-cooled TAD734GE diesel engine
Prime power (PRP): 200kVA
Ideal for business applications
Dimensions (LxWxH): 3400mm x 1400mm x 2150mm
Dry Weight: 3000kg
Starts & Stops Automatically
Maintenance-free Battery
Silent Weatherproof Mild-steel Canopy
Long-range Fuel Tank
Easy Cable Entry
Emergency Stop Button
Weatherproof Exhaust System. EngineSpecifications
Diesel generator model TAD733GE
Engine make Volvo Penta / Volvo Diesel Engine
Displacement 7.15l
Cylinder bore/Stroke 108mm x 130mm
Fuel system In-line fuel injection pump
Fuel pump Electronic fuel pump
Cylinders Six (6) cylinders, water cooled
Engine output power at 1500rpm 177kW
Turbocharged or normally aspirated Turbocharged
Cycle Four stroke
Combustion system Electronic unit injectors
Compression ratio 18.1:1
Fuel tank capacity 670l
Fuel consumption 100% 45.51 l/h
Fuel consumption 75% 33.38 l/h
Fuel consumption 50% 22.86 l/h
Fuel consumption 25% 12.01 l/h
Oil type 15W40
Oil capacity 34l
Cooling method Water-cooled radiator and fan
Coolant capacity (engine only) 37.1l
Starter 24v DC and charge alternator
Governor system Electronic
Engine speed 1500rpm
Filters Replaceable fuel filter, oil filter and dry element air filter
Battery Maintenance-free battery including rack and cables
Silencer Exhaust silencer
CHASSIS
The complete generator set is mounted as a whole on a heavy duty fabricated, steel base frame
Steel chassis and anti-vibration pads
Base frame design incorporates an integral fuel tank
The generator can be lifted or carefully pushed/pulled by the base frame
Dial type fuel gauge on the fuel tank
GENERATOR
CANOPY
Ventilation parts are designed with modular principles
Weather resistant and lined with sound reducing foam
All metal canopy parts are painted by powder paint
Panel window
Lockable doors on each side
Easy maintenance and operation
Easy lifting and moving
Thermally insulated engine exhaust system
Exterior emergency stop push button
Sound attenuated
*All ratings are quoted at maximum ratings at sea level and derating will be applicable for altitude and power factor.
GENERATOR
CONTROL SYSTEM
Control supervision and protection panel is mounted on the genset base frame. The control panel is equipped as follows:
Auto mains failure control panel
Controller with Smartgen automatic transfer switch
HGM7220 Smartgen electronic controller
Emergency stop push button
Static battery charger
Three-pole electrically and mechanically interlocked ATS
Generating set control module HGM7220 Smartgen features
This module is used to monitor a mains supply and automatically start a standby generating set
Shutdown alarms
STOP/RESET-MANUAL-AUTO-TEST-START
Metering via LCD display
Mains volts (L-L/L-N)
Generator amps (L1, L2, L3)
Generator frequency; generator (cos)
Engine hours run; plant battery (volts)
Engine oil pressure (psi and bar)
Engine speed (rpm)
Engine temperature (degrees C)
Automatic shutdown and fault conditions
Under/over speed; fail to start
High engine temperature; fail to stop
Low oil pressure; charge fail
Under/over generator volts
Under/over generator frequency;
Emergency stop/start failure
Under/over mains voltage
Charge failure